60W 24VDC High Efficiency DIN Rail Industrial Power Supply for Harsh Environments
| Output Voltage: | 24VDC | Output Current: | 2.5A |
| Output Power: | 60W | Input Voltage: | 90-264VAC |
| Frequency Range: | 47Hz-63Hz | Efficiency: | >89.0%@ 230VAC |
The GWS-DP60-24 is an economical 60W DIN Rail industrial power supply conforming to German industrial standards. Suitable for installation on TS-35/7.5 or TS-35/15 rails, it features a full-range AC input from 90Vac to 264Vac and complies with EN61000-3-2 standards for EU-specified harmonic current specifications.
Utilizing a highly flame-retardant plastic housing, this power supply ensures safety, robustness, and durability. Based on natural air convection principles, the housing features numerous ventilation holes at the bottom and top to facilitate internal airflow, achieving a high conversion efficiency of 88%. This design extends the power supply's lifespan and enables reliable operation in harsh environments from -40°C to +70°C.
The unit includes comprehensive protection functions including short-circuit, overcurrent, and overvoltage protection, making it suitable for a wide variety of inductive or capacitive load applications. Its compliance with relevant industrial control equipment certifications makes it a highly competitive power supply solution for industrial applications.
| Output Specifications | |
|---|---|
| Model | GWS-DP60-24 |
| Group of Output | 1 |
| Rated Output Voltage | 24VDC |
| Factory Set Output Voltage | 22.8-25.2VDC (Vin: 220VAC / Load: 0A) |
| Output Rated Current | 2.5A |
| Output Current Range | 0-2.5A |
| Rated Output Power | 60W |
| Total Peak Output Power | 80W (Sustained for 10 seconds at 220 VAC) |
| Peak Output Current | 3.33A (Sustained for 10 seconds at 220 VAC) |
| Ripple Noise | Peak-to-peak ≤ 200 mV |
| Output Voltage Adjustment Range | 22.4-27.4VDC |
| Stabilized Voltage Precision | ±5%(22.8VDC-25.2VDC) |
| Line Regulation | ±1% (@ 90-264VAC input, 0-100% load) |
| Load Regulation | ±5% (@90-264VAC input, 0-100% load) |
| Output Start-up Time | <3.0S @nominal input (100% load) |
| Output Hold-up Time | >20ms @115VAC, >100ms @230VAC (100% load) |
| Voltage Overshoot | ≤10% |
| Input Specifications | |
|---|---|
| Input Voltage Range | 90-264VAC |
| Rated Input Voltage Range | 100-240VAC |
| Frequency Range | 47Hz-63Hz |
| Rated Frequency | 50Hz/60Hz |
| Starting Voltage | 90VAC |
| Efficiency | >85.0%@115VAC, >88.0%@ 230VAC |
| Input Current | <1.60A@115VAC, <0.80A@ 230VAC |
| Start Inrush Current | <40A@115VAC, <50@230VAC |
| Power Factor | PF>0.5 (at full load) |
| Protection Functions | |
|---|---|
| Over-power Protection | 78-97W swing test |
| Over-voltage Protection | 30-36V swing test |
| Over-current Protection | 2.8-4.0A swing test |
| Short-circuit Protection | Automatically resumes normal operation once resolved. |
| Operation Environment | |
|---|---|
| Operation TEMP/ Humidity | -40℃~+70℃, 20%-95%RH non-condensing |
| Storage TEMP/ Humidity | -40℃~+85℃, 10%-95%RH non-condensing |
| Temperature Coefficient | ±0.03%/℃ (0-50℃) |
| Vibration | Frequency range: 10-500 Hz, acceleration: 2 G |
| Shock | Acceleration: 20 G, duration: 11 ms |
| Altitude | 5000m |
| Safety and EMC Standards | |
|---|---|
| Safety Standard | EN IEC 62368-1 |
| Insulation Strength | Input-Output: 3 kV AC/10 mA; Input-Enclosure: 1.5 kV AC/10 mA; Output-Enclosure: 0.5 kV DC/10 mA |
| Grounding Test | Test conditions: 32 A for 2 minutes; ground impedance: <0.1 Ω |
| Leakage Current | Input to ground ≤3.5 mA; input to output ≤0.25 mA |
| Insulation Resistance | Input-output: 10 MΩ |
| Electromagnetic Interference (EMI) | |
|---|---|
| Conducted Interference | EN55032, FCC Part 15 Class B |
| Radiated Interference | EN55032, FCC Part 15 Class B |
| Harmonic Current | EN61000-3-2 Class D |
| Conducted Immunity | EN61000-4-6 Level 3 |
| Radiated Immunity | EN61000-4-3 Level 3 Class B |
| Power-Frequency Immunity | EN61000-4-8 Level 3 |
| Electrostatic Immunity | EN61000-4-2 Level 4 Class B |
| Fast Pulse Groups | EN61000-4-4 Level 4 Class B |
| Lightning Strikes (Surge) | EN61000-4-5 Level 4 Class B |
| Interrupts, Dips | EN61000-4-11 |
| Physical Specifications | |
|---|---|
| Dimension | 102.5*93*41mm |
| Net /Gross Weight | 0.26kg/ 0.30kg |
| Warranty | 5 years, lifelong maintenance |
- 90~264VAC input
- 100% full load aging test
- Meets safety and EMC standards
- High efficiency, long life, and high reliability
- Operating temperature range: -40℃~+70℃
- Protection functions: short circuit/overload/overvoltage

- Factory automation
- Industrial control systems
- Electromechanical equipment
- Semiconductor manufacturing equipment
1. All specifications and parameters were measured at an input of 230 VAC, rated load, and an ambient temperature of 25°C.
2. Ripple and noise measurement method: Use a 12' twisted-pair cable with 0.1 μF and 47 μF capacitors connected in parallel at the terminals; measurements were taken at a bandwidth of 20 MHz.
3. Accuracy: Includes setting error, linear regulation, and load regulation.
4. The power supply should be considered part of the system. Electromagnetic compatibility verification must be performed in conjunction with the terminal equipment.