60W 12V DC Industrial DIN Rail Power Supply with Wide Operation Temperature Range
| Output Voltage: | 12V DC | Output Current: | 5a |
| Output Power: | 60W | Peak Power: | 80W |
| Input Voltage: | 90~264VAC | Frequency Range: | 47Hz ~ 63Hz |
| Efficiency: | >85.0% @115Vac, >88% @230Vac | Operation Temperature: | -40℃-70℃ |
| Storage Temperature: | -40°C-85°C | Dimension: | 102.5*93*41มม |
| High Light: | 60W Industrial DIN Rail Power Supply,12V DC Din Rail Mounted Power Supply,60W Din Rail Power Supply 12vdc |
||
60W/12V DIN Rail Industrial Power Supply
Overview
GWS-DP60-12 is an economical slim 60W DIN Rail industrial power supply series designed for installation on TS-35/7.5 or TS-35/15 mounting rails. The series features full-range AC input from 90VAC to 264VAC and complies with EN61000-3-2, the European Union standard for harmonic current regulation.
Constructed with a metal housing that enhances power dissipation, the GWS-DP60-12 achieves up to 89% efficiency and operates within an ambient temperature range of -40℃ to 70℃ under air convection. Equipped with a constant current mode for overload protection, it is suitable for various inductive or capacitive applications. Comprehensive protection functions and relevant industrial control certifications make the GWS-DP60-12 a highly competitive power supply solution for industrial applications.
Technical Specifications
| Model: GWS-DP60-12 | |
|---|---|
| Output | |
| Group of Output | 1 |
| DC Voltage | 12V DC |
| Output Voltage Factory Setting | 11.4-12.6VDC (Vin: 220Vac / LOAD: 0A) |
| Output Rated Current | 5A |
| Output Current Range | 0-5A |
| Output Rated Power | 60W |
| Total Peak Output Power | Up to 80W (Sustainable time 10S/220VAC) |
| Peak Output Current | 6.66A (Sustainable time 10S/220VAC) |
| Ripple noise | Peak-Peak ≤100mV (Test Method: The terminal shall be in parallel with capacitance of 0.1uF and 47uF, testing at 20MHz) |
| Output Regulation Range | DC11.8~14.2V |
| Stabilized Voltage Precision | ±5% (12.4Vdc-12.6Vdc) |
| Line Regulation | ±1% (@90-264Vac input, 0-100% load) |
| Load Regulation | ±5% (@90-264Vac input, 0-100% load) |
| Output Start Time | <3.0S @ nominal input (100% load) |
| Output Hold Time | >20ms @115Vac, >100 ms @ 230Vac (100% load) |
| Voltage Overshoot | ≤10% |
| Input | |
| Input Voltage Range | 90~264VAC |
| Input Rated Voltage Range | 100~240VAC |
| Frequency Range | 47Hz~63Hz |
| Rated Frequency | 50/60Hz |
| Starting Voltage | 90VAC |
| Efficiency | > 85.0% @ 115Vac, > 88% @ 230Vac |
| Input Current | <1.60A @ 115Vac, < 0.80A @ 230Vac |
| Startup Impulse Current | <40A @ 115Vac, <50A @ 230Vac |
| Power Factor | PF>0.5 (at full load) |
| Protection | |
| Output Overpower | 78~97W Swing machine (Testing method: Increase the output current until enabling the protection. Protection mode: Swing machine, Self-recovery after over-power released.) |
| Output Overvoltage | 18~24V Swing machine (Short circuit the Pin1-2 of U8, swing machine. Output recovery to normal after removing the short circuit). Note: Do not use external voltage. |
| Output Overcurrent | 6.0~8.5A Swing machine (Testing method: Increase the output current until enabling the protection. Protection mode: Swing machine, Self-recovery after over-current released.) |
| Output Short circuit | It achieves the long-term short circuit by connecting a sufficient cross-sectional area copper cable (Length at 15cm±5cm) with the power output port. Self-recovery to normal after removing the short circuit. |
| Operation Environment | |
| Operation TEMP/ Humidity | -40℃-70℃, 20%-95%RH |
| Storage TEMP/ Humidity | -40℃-85℃, 10%-95%RH non-condensing |
| Temperature Coefficient | ±0.03%/℃ (0-50℃) |
| Libration | Frequency range: 10~500Hz, Acceleration: 2G, Each sweep cycle 10min. Six sweeps along the X, Y, and Z axes |
| Surge | Acceleration: 20G, Duration time: 11mS, Three shocks along X, Y, and Z axes |
| Altitude | 5000m |
| Safety and EMC Standard @25℃ | |
| Security Standard | EN62368-1 |
| Dielectric Strength | Input-Output: 3KVAC/10mA, Input-Case:1.5KVAC/10mA. Output-Case:0.5KVDC/10mA, Time for each testing is 1min. |
| Grounding Test | Test Condition: 32A/2min, Ground bond: <0.1 ohms. |
| Leakage Current | Input to GND≤3.5mA, Input to output ≤0.25mA (Input 264Vac, 63Hz) |
| Insulation Resistance | Input-Output: 10M ohms |
| EMI Conducted Interference | EN55032, FCC PART 15 CLASS B |
| EMI Radiated Interference | EN55032, FCC PART 15 CLASS B |
| Harmonic Current | EN61000-3-2 CLASS D |
| EMS Conducted Emission | EN61000-4-6 Level3 |
| EMS Radiated Emission | EN61000-4-3 Leve3 criterion B |
| EMS Power Frequency Emission | EN61000-4-8 Level3 |
| EMS Electrostatic Emission | EN61000-4-2 Level4 criterion B |
| EMS EFT | EN61000-4-4 Level4 criterion B |
| EMS Surge | EN61000-4-5 Level4 criterion B |
| EMS Dip and Interruption | EN61000-4-11 |
| Others | |
| Dimension | 102.5*93*41mm |
| Warranty | 5 years |
Features
- Complies with EMC Standards
- 100% full load aging test
- Power Input: AC90-264V
- Operation temperature: -40℃ to 70℃
- High efficiency, long lifespan, and high reliability
- Provides protection against short circuit, overcurrent, and overvoltage
Applications
- Factory automation
- Industrial Control Systems
- Electro-mechanical apparatus
- Semiconductor fabrication equipment
Dimension