Metal Constructed 24W 12VDC Industrial Power Supply Slim Type DIN Rail Mounted
| Output Voltage: | 12VDC | Output Current: | 2A |
| Output Power: | 24W | Input Voltage: | 90~264VAC |
| Efficiency: | >85.0% @115Vac, >84.0% @230Vac | Operation Temperature: | -40℃~70℃ |
| Ripple Noise: | ≤100mV | Dielectric Strength: | Input-Output: 3KVac/10mA, Input-Case:1.5KVac/10mA, Output-Case:0.5KVDC/10mA |
| Dimension: | 103*82.5*23mm | Power Factor: | >0.6 (at Full Load) |
| High Light: | 12V DIN Rail Industrial Power Supply,12v Din Rail Power Supply,Slim Type Industrial Power Supply |
||
GWS-DP24-12 is an economical slim 24W DIN Rail industrial power supply series designed for installation on TS-35/7.5 or TS-35/15 mounting rails. The series features full-range AC input from 90VAC to 264VAC and complies with EN61000-3-2, the European Union standard for harmonic current regulation.
Constructed with a metal housing that enhances power dissipation, the GWS-DP24-12 achieves working efficiency up to 85% and operates in ambient temperatures from -40℃ to 70℃ with air convection. It includes constant current mode for overload protection, making it suitable for various inductive or capacitive applications. Comprehensive protection functions and relevant industrial control certifications make the GWS-DP24-12 a competitive power supply solution for industrial applications.
| Model: GWS-DP24-12 | |
|---|---|
| Output | |
| Group of Output | 1 |
| DC Voltage | 12VDC |
| Default Output Voltage | 12.00-12.2V (VIN: 220VAC / LOAD: 0A) |
| Output Rated Current | 2A |
| Output Current Range | 0-2A |
| Output Rated Power | 24W |
| Total Peak Output Power | Up to 36W (Sustainable time 10S/220VAC) |
| Peak Output Current | 3A (Sustainable time 10S/220VAC) |
| Ripple Noise | Peak-Peak ≤100mV (Test Method: The terminal shall be in parallel with capacitance of 0.1uF and 47uF, testing at 20MHz) |
| Output Regulation Range | 10.V~15.0V |
| Stabilized Voltage Precision | ±1% (@90-264Vac input, 100% load) |
| Line Regulation | ±0.5% (@90-264Vac input, 100% load) |
| Load Regulation | ±1% (@90-264Vac input, 100% load) |
| Temperature Coefficient | ±0.03%/℃ (0-50℃) |
| Output Start Time | <3S@115Vac, <1.6S @230Vac (100% load) |
| Output Hold Time | >20ms@230Vac (100% load) |
| Voltage Overshoot | ≤5% |
| Input | |
| Input Voltage Range | 90~264VAC |
| Input Rated Voltage Range | 100~240VAC |
| Frequency Range | 47Hz~63Hz |
| Rated Frequency | 50/60Hz |
| Starting Voltage | 90Vac |
| Efficiency | >85.0% @115Vac, >84.0% @230Vac |
| Input Current | <0.60A @115Vac, <0.30A @230Vac |
| Inrush Starting Current | <60A @ 230Vac |
| Power Factor | PF>0.6(at full load) |
| Protection | |
| Output Over Power | 28.8~36W Swing machine (Testing method: Increase the output current until enabling the protection. Protection mode: Swing machine, Self-recovery after over-power released.) |
| Output Over Voltage | 15~16V Swing machine (Short circuit the Pin1-2 of U8, swing machine. Output recovery to normal after removing the short circuit). Note: Do not use external voltage. |
| Output Over Current | 2.4~3.0A Swing machine (Testing method: Increase the output current until enabling the protection. Protection mode: Swing machine, Self-recovery after over-current released.) |
| Output Short Circuit | It achieves the long-term short circuit by connecting a sufficient cross-sectional area copper cable (Length at 15cm±5cm) with the power output port. Self-recovery to normal after removing the short circuit. |
| Operation Environment | |
| Operation Temp/ Humidity | -40~70℃, 20%~95%RH |
| Storage Temp/ Humidity | -40℃~85℃, 10%~95%RH non-condensing |
| Libration | Frequency range: 10~500Hz, Acceleration: 2G, Each sweep cycle 10min. Six sweeps along the X, Y, and Z axes |
| Surge | Acceleration: 20G, Duration time: 11mS, Three shocks along X, Y, and Z axes |
| Altitude | 2000m |
| Safety and EMC Standard @25℃ | |
| Security Standard | EN62368-1 |
| Dielectric Strength | Input-Output: 3KVac/10mA, Input-Case:1.5KVac/ 10mA, Output-Case:0.5KVDC/10mA, Time for each testing is 1min. |
| Grounding Test | Test Condition: 32A/2min, Ground bond:<0.1 ohms. |
| Leakage Current | Input to GND≤3.5mA, Input to output ≤0.25mA (Input 264Vac, 63Hz) |
| Insulation Resistance | Input-Output: 10M ohms |
| EMI Conducted Interference | EN55032, FCC PART 15 CLASS B |
| EMI Radiated Interference | EN55032, FCC PART 15 CLASS B |
| Harmonic Current | EN61000-3-2 CLASS D |
| EMS Conducted Emission | EN61000-4-6 Level3 |
| EMS Radiated Emission | EN61000-4-3 Leve3 criterion B |
| EMS Power Frequency Emission | EN61000-4-8 Level3 |
| EMS Electrostatic Emission | EN61000-4-2 Level4 criterion B |
| EMS EFT | EN61000-4-4 Level4 criterion B |
| EMS Surge | EN61000-4-5 Level4 criterion B |
| EMS Dip and Interruption | EN61000-4-11 |
| Others | |
| Dimension | 103*82.5*23mm |
- Meets EMC Standards
- 100% full load aging test
- Power Input: AC90~264V
- Operation temperature: -40℃~70℃
- High efficiency, long lifetime, and high reliability
- Short circuit/overcurrent/overvoltage protection
- Factory automation
- Industrial Control System
- Electro-mechanical apparatus
- Semiconductor fabrication equipment